← Back to home
ICSA-11-122-01  ·  Published 2025-06-25  ·  View on CISA ICS-CERT ↗

AzeoTech DAQFactory Networking Vulnerabilities

CVSS 7.5 HIGH

CVEs (1)

Remediations

  • AzeoTech recommends that users take one of the following steps to secure their systems: Upgrade to Version 5.85 (Build 1842), which addresses this vulnerability by adding authentication, and changes default settings to disable both the networking feature and also the remote reboot and shutdown feature. Users can download Version 5.85 at: (http://www.azeotech.com/downloads.php). For versions older than Version 5.85, disable the DAQFactory networking feature if the system configuration does not require network support. Users can check the “Disable Broadcast” option in the “File - Document Settings” menu. AzeoTech recommends that DAQFactory only be deployed on an isolated network when one of the above mitigation steps cannot be performed.

Affected Vendors

AzeoTech

Affected Products (4)

AzeoTech · DAQFactory Standard vers:all/*
AzeoTech · DAQFactory Pro vers:all/*
AzeoTech · DAQFactory Developer vers:all/*
AzeoTech · DAQFactory Runtime vers:all/*

Get alerted to advisories like this

OTWarden monitors CISA, BSI, Siemens, Rockwell and more — and emails you within 2 hours when your vendors are affected.

Start free trial Learn more