Schneider Electric Easergy T300

CVSS 10.0 CRITICAL

Risk Summary

Successful exploitation of this vulnerability could allow an attacker to obtain unauthorized access to the internal product LAN, which could result in exposure of sensitive information, denial of service, and remote code execution when access to a resource from an attacker is not restricted or incorrectly restricted.

Remediations

  • Schneider Electric recommends users upgrade to v2.7.1, which is available from the Schneider Electric Customer Care Center. Alternatively, users may disable port forwarding in the product firewall.
  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in “Program” mode.
  • Never connect programming software to any network other than the network for which the devices are intended.
  • Scan all methods of mobile data exchange with the isolated network (e.g., CDs, USB drives, etc.) before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network, besides the intended network, to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
  • For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
  • Refer to Schneider Electric's security bulletin SEVD-2020-315-06 for specific mitigation details.

Affected Vendors

Schneider Electric Software, LLC

Affected Products (1)

Schneider Electric Software, LLC · Easergy T300 with firmware <= 2.7

Affected Sectors

Commercial Facilities, Energy, Food and Agriculture, Government Facilities, Transportation Systems, Water and Wastewater Systems